VLT® Advanced Harmonic Filter AHF 005/AHF 010

Shows 172 product(s)

AHF-DA-048-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3276
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5905
Back plate: 130B3285
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 048A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X3

AHF-DA-060-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3277
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5906
Back plate: 130B3286
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 060A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X4

AHF-DA-073-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3277
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5906
Back plate: 130B3286
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 073A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X4

AHF-DA-095-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3278
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5907
Back plate: 130B3287
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 095A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X5

AHF-DA-118-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3278
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5907
Back plate: 130B3287
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 118A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X5

AHF-DA-154-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3279
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5908
Back plate: 130B3287
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 154A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X6

AHF-DA-183-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3279
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5908
Back plate: 130B3287
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 183A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X6

AHF-DA-231-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3281
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5909
Back plate: 130B3288
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 231A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X7

AHF-DA-291-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3281
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5909
Back plate: 130B3288
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 291A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X7

AHF-DA-355-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3281
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5909
Back plate: 130B3288
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 355A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X7

AHF-DA-436-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF 010 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 10% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3282
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B6101
Back plate: 130B3288
Specifications:
THiD less than 10%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 436A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X8

AHF-DB-010-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3274
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5903
Back plate: 130B3283
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 010A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Cooled by natural convection
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X1

AHF-DB-014-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3274
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5903
Back plate: 130B3283
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 014A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X1

AHF-DB-019-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3275
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5904
Back plate: 130B3284
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 019A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X2

AHF-DB-025-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3275
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5904
Back plate: 130B3284
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 025A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X2

AHF-DB-031-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3276
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5905
Back plate: 130B3285
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 031A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X3

AHF-DB-036-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3276
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5905
Back plate: 130B3285
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 036A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X3

AHF-DB-048-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3276
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5905
Back plate: 130B3285
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 048A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X3

AHF-DB-060-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3277
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5906
Back plate: 130B3286
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 060A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X4

AHF-DB-073-460-60-20-A

The VLT® Advanced Harmonic Filter is a passive harmonic filter specially designed to match the Danfoss frequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC Drive. With AHF005 connected in front of the Danfoss VLT® the harmonic current distortion generated back to the mains is reduced to maximum 5% at full load.
[!]Forced cooling is not included within IP00 types. Cooling must be secured separately during installation.
Accessories:
IP20 to Type 1/NEMA conversion kit: 130B3277
IP20 to Type 1/NEMA conversion kit with capacitor disconnect: 130B5906
Back plate: 130B3286
Specifications:
THiD less than 5%
Line voltage: 440-480V
Line frequency: 60Hz
Filter current: 073A
Line voltage tolerances: +/- 10%
Line frequency tolerances: +5% / -1.5%
Overload capacity: 160% for 60 sec. every 10 min.
Enclosure rating: 20
Cooling concept: Forced cooled by build-in fan
Efficiency: > 98%
Ambient temperature without derating: 5-45 ºC
Enclosure: X4