175U0318
VLT® Line reactor MCC 103 - line reactor for load sharing
MCC 103 line reactor is specially designed to match the Danfossfrequency converters VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVACDrive in applications using load sharing. Use the MCC 103 line reactorfor up to 500V mains supply with 50 Hz or 60 Hz mains frequency. The MCC103 line reactor is available with IP00 enclosure protection.
Specifications:,
Rated voltage:,380-500 V
Rated frequency: 50-60 Hz
Rated current,104 A
Inductance L: 70 uH
Winding resistance: 1.5 mOhm
L tolerance: ±10%
Mains connection - type: Bus-bar
Mains connection - dimension: 1 x Ø7.1
Mains connection - tightening torque: - Nm
PE connection - type: Bolt connection
PE connection - dimension: M5
Ambient temperature without derating: -10 to +45 C°
Derating > 45 °C: 2.5%/K
Derating > 1km: 5%/1km
Type of cooling: Cooled by natural convection
Operating conditions: Permanent operation with 100% load
Weight: 6.9 kg
Dimensions - HxWxD: 160x185x125 mm
Enclosure degree: IP00
Mounting,: Vertical or horizontal