DST GR32, R32

073G2050

This product is not available in this store. Please contact your local Customer Service Center.

Versorgungsspannung [V] [AC]: 24, null: 24.00, Messbereich [°C]: -40 - 80, Elektr. Anschlussgröße: 6 pin, Spezifik. Schlüssel: DST GR32-B0-12-0AAB-LC001-I

Product details

Bruttovikt 58 Gram
Nettovikt 46 Gram
EAN 5715162909034

 

Alarm reset [LFL hysteresis %] 2,5
Alarm reset Relay 5 seconds
Alarm threshold [LFL %] 12
Ambient temperature range [°C] [max] 95 °C
Ambient temperature range [°C] [min] -40 °C
Ambient temperature range [°F] [min] -40 °F
Approval CE
CE evaluated Yes
Communication configuration Danfoss Default
Contain batteries No
Electrical connection size 6 pin
Electrical connection standard EN 60529
Elektrisk anslutning Mini Mate-N-Lok
Enclosure design Round Ø6 black
Enclosure rating IP IP54
Flame rating UL 94 V-0
Förpackningsformat Industripack
Husmaterial PA66 25% Glass fiber
International Article Number 5715162909034
Matningsspänning [V] AC 24 V
Measuring range [°C] [Max] 80 °C
Measuring range [°C] [Min] -40 °C
Measuring range [°F] [Max] 175 °F
Measuring range [°F] [Min] -40 °F
Modbus termination None
Mounting interface 2 brackets 180 dgr
Omgivningstemperatur, område [°F] [Max] 200 °F
Pin 1 + supply
Pin 2 - common
Pin 3 Not connected
Pin 4 Not connected
Pin 5 Relay input
Pin 6 Relay NO
Pressure range [bar] [max] 1.2 bar
Pressure range [bar] [min] 0.7 bar
Product Group Sensors
Product name Gas sensor
Quantity per packing format 80 pc
Recovery time [min] <5
Refrigerants R32
Rel. luftfuktighetsvillkor 0 - 100
Response time [S] <15
Specification key DST GR32-B0-12-0AAB-LC001-I
Strömförsörjning max. [mA] 300 mA
Supply voltage [V] DC 24 V
Tryckområde [psi] [Max] 17.4 psi
Tryckområde [psi] [Min] 10.15 psi
Type DST GR32
Utgångssign. Relay

Accessories

Spare Parts

Replacement

Replacement

Replacement

Services

Software

Software and firmware to extend functionality