VLT® Advanced Harmonic Filter AHF 005/AHF 010

Zeigt 172 Produkt(e)

130B1488

AHF-DA-048-460-60-20-A

VLT® Advanced Harmonic Filter - AHF 010
The Danfoss Advanced Harmonic Filter is a compact passive harmonic
filter specially designed to match the Danfoss frequency converters
VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC/R Drives.
The program offers two variants, AHF 005 and AHF 010.Connected in
front of the Danfoss VLT® frequency converter, the harmonic current
distortion on the line is reduced to 5% or 10% at nominal load.
Specifications:
Line voltage: 440-480V
Line frequency: 60Hz
Nominal current: 48A
THDi Less than 10%
Cooling concept: Integrated fan with variable speed
Efficiency: > 98 %
Ambient temperature: 5-45 deg C
Enclosure type: X3-V3 IP20 if
Enclosure degree: IP20 (IP21 / NEMA 1 optional)
Dimensions:
Height: 592mm
Width: 378mm
Depth: 245mm
Accessories:
IP21 / NEMA1 Kit for AHF3 X3 : 175U3276
IP21/NEMA1 Kit for AHF3 X3 with capacitor disconnect option:175U5905
Backplate for AHF X3 : 130B3285

130B1491

AHF-DA-060-460-60-20-A

Oberschwingungs-Netzfilter für VLT AQUA Drive,
VLT HVAC Drive und VLT AutomationDrive (HO),
440 - 480V, P37K zur Reduzierung der
Netzrückwirkungen, Oberschwingungsstrom THiD <
10%.
Nennstrom: 60A
Überlastbarkeit: 1,6 fach für 60s
Netzspannung: 440 - 480V (± 10%)
Netzfrequenz: 60Hz ± 5 %
Netzvoraussetzung: Rsce > 66 und THD U < 2%
Wirkungsgrad: ca. 98 %
Schutzart: IP 20
Umgebungstemperatur: 5° C…40° C
Physikalische Abmessungen (HxBxT): 490 x 378 x333
Gewicht: 52 kg

130B1492

AHF-DA-073-460-60-20-A

Oberschwingungs-Netzfilter für VLT AQUA Drive, VLT HVAC Drive und VLT
AutomationDrive (HO),
440 - 480V, P45K zur Reduzierung der
Netzrückwirkungen,
Oberschwingungsstrom THiD <(><<)> 10%
Nennstrom: 73A
Überlastbarkeit: 1,6 fach für 60s
Netzspannung: 440 - 480V (± 10%)
Netzfrequenz: 60Hz ± 5 %
Netzvoraussetzung: Rsce > 66 und THD U <(><<)> 2%
Wirkungsgrad: ca. 98 %
Schutzart: IP 20
Umgebungstemperatur: 5° C…40° C
Physikalische Abmessungen (HxBxT): 577 x 378 x 333
Gewicht: 56 kg

130B1493

AHF-DA-095-460-60-20-A

VLT® Advanced Harmonic Filter - AHF 010

The Danfoss Advanced Harmonic Filter is a compact passive harmonic
filter specially designed to match the Danfoss frequency converters
VLT® AutomationDrive, VLT® AQUA Drive and VLT® HVAC/R Drives.
The program offers two variants, AHF 005 and AHF 010.Connected in
front of the Danfoss VLT® frequency converter, the harmonic current
distortion on the line is reduced to 5% or 10% at nominal load.

Specifications:
Line voltage: 440-480V
Line frequency: 60Hz
Nominal current: 95A
THDi Less than 10%
Cooling concept: Integrated fan with variable speed
Efficiency: > 98 %
Ambient temperature: 5-45 deg C
Enclosure type: X5-V3 IP20 ef
Enclosure degree: IP20 (IP21 / NEMA 1 optional)
Dimensions:
Height: 736mm
Width: 418mm
Depth: 333mm

Accessories:
IP21 / NEMA1 Kit for AHF3 X5 : 175U3278
IP21/NEMA1 Kit for AHF3 X5 with capacitor disconnect option:175U5907
Backplate for AHF X5/X6 : 130B3287

130B1494

AHF-DA-118-460-60-20-A

Oberschwingungs-Netzfilter für VLT AQUA Drive, VLT HVAC Drive und VLT
AutomationDrive (HO),
440 - 480V, P75K zur Reduzierung der
Netzrückwirkungen,
Oberschwingungsstrom THiD <(><<)> 10%
Nennstrom: 118A
Überlastbarkeit: 1,6 fach für 60s
Netzspannung: 440 - 480V (± 10%)
Netzfrequenz: 60Hz ± 5 %
Netzvoraussetzung: Rsce > 66 und THD U <(><<)> 2%
Wirkungsgrad: ca. 98 %
Schutzart: IP 20
Umgebungstemperatur: 5° C…40° C
Physikalische Abmessungen (HxBxT): 685 x 418 x 333
Gewicht: 74 kg

Ansicht: