Ambient temperature range [°C] [max] |
60 °C |
Ambient temperature range [°C] [min] |
-10 °C |
Ambient temperature range [°F] [Max] |
140 °F |
Ambient temperature range [°F] [Min] |
14 °F |
Category |
Art. 4, par. 3 |
China RoHS compliance |
Yes |
Compatible Danfoss controllers |
EIM 336 EKE 1A EKE 1B EKE 1C |
Connection material |
Cu-plated SS |
Connection type |
Solder, ODM |
Design config. Style |
H |
EU RoHS compliance |
Out of scope |
Flow characteristic |
Linear |
Flow direction |
Bi-flow |
In scope of WEEE and contain batteries |
No |
Inlet size [in] |
5/16 in |
Inlet size [mm] |
7.94 mm |
Lubricants compatibility |
POE |
Manual operation option |
AST-G service driver Manual coil |
Max. Working Pressure [bar] |
49 bar |
Max. Working Pressure [psig] |
711 psig |
MaxOPD [bar] |
42 bar |
MaxOPD [psig] |
609 psig |
MaxOPD reverse [bar] |
35 bar |
MaxOPD reverse [psi] |
508 psi |
Min. Leakage [cm³/min] @ 1 Mpa |
150 cm³/min |
Motor type |
Permanent magnet stepper motor |
Orifice size [mm] |
1.65 mm |
Outlet size [in] |
5/16 in |
Outlet size [mm] |
7.94 mm |
Packing format |
Multi pack |
Parts Program name |
ETS 5M |
Product accessories |
Electric valve accessories |
Product Group |
Expansion valves |
Product name |
Electric expansion valve |
Quantity per packing format |
20 pc |
Rated cap. conditions [SI] |
Subcooling=0 ºC Superheat=0 ºC tcond=38 ºC tevap=5 ºC |
Rated capacity R1234yf [kW] |
5.8 kW |
Rated capacity R1234yf [TR] |
1.65 TR |
Rated capacity R1234ze [kW] |
5.86 kW |
Rated capacity R1234ze [TR] |
1.67 TR |
Rated capacity R134a [kW] |
7.94 kW |
Rated capacity R134a [TR] |
2.26 TR |
Rated capacity R22 [kW] |
10.5 kW |
Rated capacity R22 [TR] |
2.99 TR |
Rated capacity R290 [kW] |
10.9 kW |
Rated capacity R290 [TR] |
3.1 TR |
Rated capacity R32 [kW] |
18.29 kW |
Rated capacity R32 [TR] |
5.2 TR |
Rated capacity R404A/R507 [kW] |
7.38 kW |
Rated capacity R404A/R507 [TR] |
2.1 TR |
Rated capacity R407C [kW] |
10.97 kW |
Rated capacity R407C [TR] |
3.12 TR |
Rated capacity R407H [kW] |
12.25 kW |
Rated capacity R407H [TR] |
3.48 TR |
Rated capacity R410A [kW] |
12.38 kW |
Rated capacity R410A [TR] |
3.52 TR |
Rated capacity R448A [kW] |
10.49 kW |
Rated capacity R448A [TR] |
2.98 TR |
Rated capacity R449A [kW] |
10.26 kW |
Rated capacity R449A [TR] |
2.92 TR |
Rated capacity R449B [kW] |
10.43 kW |
Rated capacity R449B [TR] |
2.97 TR |
Rated capacity R452A [kW] |
7.9 kW |
Rated capacity R452A [TR] |
2.25 TR |
Rated capacity R452B [kW] |
14.21 kW |
Rated capacity R452B [TR] |
4.04 TR |
Rated capacity R454A [kW] |
10.63 kW |
Rated capacity R454A [TR] |
3.02 TR |
Rated capacity R454B [kW] |
14.39 kW |
Rated capacity R454B [TR] |
4.09 TR |
Rated capacity R454C [kW] |
9.14 kW |
Rated capacity R454C [TR] |
2.6 TR |
Rated capacity R455A [kW] |
10.08 kW |
Rated capacity R455A [TR] |
2.87 TR |
Rated capacity R513A [kW] |
6.72 kW |
Rated capacity R513A [TR] |
1.91 TR |
Rated capacity R515B [kW] |
5.68 kW |
Rated capacity R515B [TR] |
1.62 TR |
REACH Candidate List substances 0.1 |
No |
Refrigerant temperature [ºC] [Max] |
70 °C |
Refrigerant temperature [ºC] [Min] |
-30 °C |
Refrigerant temperature [ºF] [Max] |
158 °F |
Refrigerant temperature [ºF] [Min] |
-22 °F |
Refrigerants |
R1234yf R1234ze(E) R134a R22 R290 R32 R404A/R507A R407C R407H R410A R448A R449A R449B R452A R452B R454A R454B R454C R455A R463A R513A R515B |
Relative humidity (RH) [%] [Max] |
95 % |
Relative humidity (RH) [%] [Min] |
0 % |
Serviceable |
No |
Step mode |
1-2 excitation (half step) 2-2 excitation (full step) |
Storage temperature range [°C] [Max] |
70 °C |
Storage temperature range [°C] [Min] |
-30 °C |
Storage temperature range [°F] [Max] |
158 °F |
Storage temperature range [°F] [Min] |
-22 °F |
Total steps |
480 (half steps) |
Type |
ETS 5M17 |
UK RoHS compliance |
Out of scope |
Valve open pulses@normal flow |
55 ± 16 steps |
Valve open pulses@reverse flow |
15 ± 15 steps |