Thermostat, KPS83

060L310966

Temperature range [°C]: 100 - 200, Reset function: Auto, Contact function: SPDT gold, Sensor type: Remote bulb, Capillary tube length [mm]: 2000, Enclosure rating IP: IP67

Product details

Gross weight 1.088 Kilogram
Net weight 1.002 Kilogram
Volume 3.684 Liter
EAN 5702423147632

 

Amb. Temp. Note 80 °C/176 °F for max 120 min
Ambient temperature range [°C] [max] 70 °C
Ambient temperature range [°C] [min] -40 °C
Ambient temperature range [°F] [Max] 158 °F
Ambient temperature range [°F] [Min] -40 °F
Approval ABS
BV
CCC
CCS
CE
DNV
EAC
GL
LLC CDC EURO-TYSK
LR
LVD
NKK
RINA
RMRS
RoHS
RoHS China
TYSK
UKCA
UL
Cap. tube length fraction [in] 78 3/4 in
Capillary tube length [mm] 2000 mm
CE evaluated Yes
Charge type Adsorption
China RoHS compliance Yes
Connection for pocket or hose M 18 x 1.5
Contact function SPDT gold
Contact rating AC15=4 A, 440 V
AC1=10 A, 440 V
AC3=6 A, 440 V
DC13=12 W, 220 V
for gold 1…30mA, 5...30V
Diff. @ Min. range setting [K] [Max] 30 K
Diff. @ Min. range setting [K] [Min] 6.5 K
Diff. @ Min. range setting[°C] [Max] 30 °C
Diff. @ Min. range setting[°C] [Min] 6.5 °C
Differential type Adjustable
Electrical conn. comments Metal cable gland
Electrical conn. Male/Female Female
Electrical connection Screwed cable entry
Electrical connection size Pg 13.5
Electrical connection standard DIN 40430
Electrical spec. standard EN 60947-5
EN 60947 electrical properties Insulation: 400V
Pollution degree: 3
Rated impulse voltage: 4 kV
Short circuit prot, fuse: 16A
EN 60947 wiring properties Flex, ferrules: 0.5-1.5 mm2
Flex, no ferrules: 0.7-2.5 mm2
Solid/stranded: 0.75-2.5 mm2
Enclosure rating IP IP67
EU RoHS compliance Out of scope
In scope of WEEE and contain batteries No
Max. sensor temperature [°C] 300 °C
Max. sensor temperature [°F] 572 °F
Packing format Multi pack
Product accessories Switches accessories
Product description Thermostat
Product Group Switches and thermostats
Product name Thermostat
Quantity per packing format 10 pc
REACH Candidate List substances 0.1 Lead (CAS no. 7439-92-1)
Reset function Auto
SCIP dossier no. 84be8326-1b95-4f87-afb0-90ae08b65f06
Sensor pocket length min. [in] 3 in
Sensor pocket length min. [mm] 75 mm
Sensor size (Ø x L) [in] 1/2 x 2 1/2 in
Sensor size (Ø x L) [mm] 13 x 63 mm
Sensor type Remote bulb
Serviceable No
Temperature range [°C] [Max] 200 °C
Temperature range [°C] [Min] 100 °C
Temperature range [°F] [Max] 392 °F
Temperature range [°F] [Min] 212 °F
Type KPS83
UK RoHS compliance Out of scope
UL approval file name E73170
UL evaluated Yes

Accessories

Spare Parts

Replacement

Replacement

Replacement

Services

Software

Software and firmware to extend functionality