VACON® dU/dt Filter

26 produit(s) trouvé(s)

141F1098

DUT filter 12A 690V IP21

DUT-0012-6-2-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 12 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V - 690V
Typical losses: 65 W
Degree of protection: IP21
Dimensions H x W x D: 265 x 195 x 145 mm
Weight: 6,4 kg

141F1112

Du/dt filter

DUT-0100-6-5-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 100 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V -
690V
Typical losses: 110 W
Degree of protection: IP54
Dimensions H x W x D: 645 x 456 x 215 mm
Weight: 35 kg

141F1121

Du/dt filter

DUT-0350-6-0-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 350 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V - 690V
Typical losses: 410 W
Degree of protection: IP00
Dimensions H x W x D: 299 x 300 x 236 mm
Weight: 50 kg

141F1127

Du/dt filter

DUT-0600-6-0-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 600 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V - 690V
Typical losses: 580 W
Degree of protection: IP00
Dimensions H x W x D: 449 x 300 x 243 mm
Weight: 76 kg

141F1140

DUT-1250-6-0-S, Du/dt 1250A 690V IP00

DUT-1250-6-0-S
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 1250 A
Max output frequency: 70 Hz without derating / 135 Hz with derating
Nominal switching frequency fs : 4 kHz @ 200V - 500V, 2 kHz @ 525 V -
690V
Cooling: Forced cooled with integrated fan.
Cable length: max 300m (@ nominal fs)
Degree of protection: IP00
Dimensions H x W x L: 190 x 475 x 745 mm
Weight: 95 kg

141F1142

DUT-1500-6-0-P Du/dt 1500A 690V IP00

DUT-1500-6-0-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 1500 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V - 690V
Typical losses: 1100 W
Degree of protection: IP00
Dimensions H x W x D: 599 x 480 x 358 mm
Weight: 190 kg

141F1150

DUT-2300-6-0-P, Du/dt 2300A 690V IP00

DUT-2300-6-0-P
dU/dt filter for VACON NX.
Voltage: 200 V - 690 V
Continuous current: 2300 A
Max output frequency: 70 Hz without derating / 320 Hz with derating
Max switching frequency fs : 3,6 kHz @ 200V - 500V, 1,5 kHz @ 525 V - 690V
Typical losses: 2900 W
Degree of protection: IP00
Dimensions H x W x D: 693 x 660 x 381 mm
Weight: 420 kg

Afficher: