Ambient temperature max. [°C] |
85 °C |
Ambient temperature max. [°F] |
185 °F |
CE evaluated |
Yes |
China RoHS compliance |
Yes exceed limitations |
Connection material |
AISI 316 Ti |
Connection standard |
ISO 228 |
Connection type |
G |
Contain batteries |
No |
EEE category |
5 small equipment (any external dimension < 50 cm) |
Electrical conn. Male/Female |
Male and Female |
Electrical connection |
Angular connector |
Electrical connection size |
Pg 9 |
Electrical connection standard |
EN 175301-803-A |
Enclosure rating IP |
IP65 |
EU RoHS compliance |
Yes with exemptions |
EU RoHS exemption clause |
6(a) 6(b) 6(c) 7(a) 7(c)-I |
In scope of WEEE |
Yes |
Insertion length [in] |
5.9 in |
Insertion length [mm] |
150 mm |
Insertion type |
FIXED |
Output signal [mA] [Max] |
20 mA |
Output signal [mA] [Min] |
4 mA |
Packing format |
Multi pack |
Process connection Male/Female |
Male |
Process connection material |
Stainless steel |
Process connection size |
1/4 |
Process connection standard |
ISO 228-1-A |
Process connection type |
G |
Product group |
Sensors |
Product name |
Temperature transmitter |
Protection tube diameter [in] |
0.315 in |
Protection tube diameter [mm] |
8 mm |
Protection tube material |
AISI 316 Ti |
Quantity per packing format |
13 pc |
REACH Candidate List substances |
Lead (CAS no. 7439-92-1) Dodecamethylcyclohexasiloxane (D6, CAS no. 540-97-6) |
Sensor elem. resistance [Ohm] |
1000 |
Sensor element tolerance |
< ± 1% FS |
Sensor element type |
Pt |
Sensor Insert |
FIXED |
Supply voltage [V] DC [max] |
32 V |
Supply voltage [V] DC [min] |
10 V |
Temperature range [°C] [Max] |
200 °C |
Temperature range [°C] [Min] |
-50 °C |
Temperature range [°F] [Max] |
392 °F |
Temperature range [°F] [Min] |
-58 °F |
Transmitter setting range [°C] [Max] |
100 °C |
Transmitter setting range [°C] [Min] |
0 °C |
Transmitter setting range [°F] [Max] |
212 °F |
Transmitter setting range [°F] [Min] |
32 °F |
Transmitter type |
Integrated |
Type |
MBT 5560 |
Type designation |
MBT 5560-0000-0150-10-110 |
UK RoHS compliance |
Yes with exemptions |
UK RoHS exemption clause |
12 15 18 19 21 |