Ambient temperature range [°C] [max] |
65 °C |
Ambient temperature range [°C] [min] |
-20 °C |
Ambient temperature range [°F] [max] |
149 °F |
Ambient temperature range [°F] [min] |
-4 °F |
Approval |
ATEX - Cat. 2 - Zone 1 CCC CE EAC LLC CDC EURO-TYSK PZH RMRS RoHS RoHS China TYSK |
Burst pressure [bar] |
88 bar |
CE evaluated |
Yes |
China RoHS compliance |
Yes |
Contact function |
SPDT gold |
Contact rating |
Ci=0.5 nF Ii=0.5 A Li=0.2 uH Pi=1 W Ui=29 V |
Differential [bar] [max] |
1.6 bar |
Differential [bar] [min] |
0.5 bar |
Differential [psi] [max] |
23.2 psi |
Differential [psi] [min] |
7.3 psi |
Electrical conn. Male/Female |
Female |
Electrical connection |
Screwed cable entry |
Electrical connection size |
2xPg 13.5 |
Electrical connection standard |
DIN 40430 |
Electrical spec. standard |
EN 60947-4/-5 |
EN 60947 electrical properties |
Insulation: 400V Pollution degree: 3 Rated impulse voltage: 4 kV Short circuit prot, fuse: 10A |
EN 60947 wiring properties |
Flex, ferrules: 0.2-1.5 mm2 Flex, no ferrules: 0.2-2.5 mm2 Solid/stranded: 0.2-2.5 mm2 |
Enclosure rating IP |
IP66 |
EU RoHS compliance |
Out of scope |
EX Sales text |
-20Cta+65C II 2G Ex ia IIC T6...T1 Gb |
In scope of WEEE and contain batteries |
No |
Max. test pressure [bar] Pe |
25 bar |
Max. test pressure [psig] |
363 psig |
Max. Working Pressure [bar] |
22 bar |
Max. Working Pressure [psig] |
320 psig |
Packing format |
Multi pack |
Pressure connection notes |
Weld nipple d6.5/D10mm |
Pressure connection size |
3/8 |
Pressure connection standard |
ISO 228-1 |
Pressure connection type |
G |
Pressure Male/Female |
Male |
Pressure sensing element |
Bellows |
Product accessories |
Switches accessories |
Product description |
Pressure Switch |
Product group |
Switches and thermostats |
Product Name Description |
Pressure switch |
Quantity per packing format |
15 pc |
REACH Candidate List substances |
Lead (CAS no. 7439-92-1) |
Regulation range |
23.6 inHg - 72.5 psig |
Regulation range [bar] Pe [max] |
5 bar |
Regulation range [bar] Pe [min] |
-0.8 bar |
Reset function |
Auto |
SCIP dossier no. |
54f3e4b2-77e8-4825-a1c1-c3d5ba584171 |
Serviceable |
Contact systems |
Type |
RT1AE |
UK RoHS compliance |
Out of scope |