ECL Comfort 110, Supply voltage [V] AC: 207 - 244, Time switch type: No time switch

087B1261

ECL Comfort 110 - 230 V a.c.

Product details

Gross weight 0.556 Kg
Net weight 0.535 Kg
Volume 2.155 Liter
EAN 5702421067727

 

Actuator output load [VA] 15 VA
Ambient humidity [% RH] [Max] 65 %
Ambient temperature [°C] [Max] 55 °C
Ambient temperature [°C] [Min] 0 °C
Application source On-board
Approval CE
Approval standard EMC-Directive: 2004/108/EC
Emission: EN 61000-6-3:2007
Immunity: EN 61000-6-1:2007
LVD directive 2006/95/EC
Communications ECL-Bus (non-galvanically isolated)
Description ECL Comfort 110 - 230 V a.c.
DHW functions Auto-tunning
Return temperature influence
Display type LCD custom design
EU RoHS compliance Yes with exemptions
General functions Circulation pump exercise
Control valve exercise
External override facility
Frost protection
Master - Slave network
Motor protection
Remote control connection
Grade of enclosure IP41
Heat curve setting for heating circuit Slope
In scope of WEEE and contain batteries No
Number of 3-point motor control outputs 1
Number of DHW circuits 1
Number of digital inputs 1
Number of heating circuits 1
Number of pumps 1
Number of relay outputs 1
Number of Sensor inputs 4 pc
Power consumption [W] 3 W
Product Group Electronic controllers
REACH Candidate List substances 0.1 Lead (CAS no. 7439-92-1)
Relay output inductive load [A] 2 A
Relay output ohmic load [A] 4 A
Relay output voltage [V] AC 230 V
Sensor cable length [m] 125 m
Sensor cable length [mm] 125 mm
Storage temperature [°C] [Max] 70 °C
Storage temperature [°C] [Min] -40 °C
Supply voltage [V] AC 230 V
Supply voltage [V] AC [max] 244 V
Supply voltage [V] AC [min] 207 V
Supply voltage frequency [Hz] 50 Hz
Temperature sensors type Pt 1000
Time switch power backup [h] 12 h
Time switch type No time switch
Type ECL Comfort 110
User input type Display
Push buttons

Accessories

Spare Parts

Replacement

Replacement

Replacement

Services

Software

Software and firmware to extend functionality